Eastron SDM Modbus 解析器库

项目描述

sdm_modbus

sdm_modbus 是一个 python 库,它通过 Modbus RTU 或 Modbus TCP 从 Eastron SDM 单相和三相 kWh 电表收集数据。

支持的设备:

安装

要安装,请克隆此项目并使用以下命令安装poetry

poetry install

或从 PyPi 安装软件包:

pip3 install sdm_modbus

用法

该脚本提供了一个通过Modbus TCPexample-tcp.py连接并显示SDM120上的所有输入和保持寄存器的最小示例。要将值显示为 JSON 对象,请添加.--json

usage: example-tcp.py [-h] [--unit UNIT] [--json] host port

positional arguments:
  host         Modbus TCP address
  port         Modbus TCP port

optional arguments:
  -h, --help   show this help message and exit
  --unit UNIT  Modbus device address
  --json       Output as JSON

输出:

SDM120(10.0.0.123:502, connectionType.TCP: timeout=1, retries=3, unit=0x1):

Input Registers:
    Voltage: 237.00V
    Current: 8.63A
    Power (Active): -1919.70W
    Power (Apparent): 2035.57VA
    Power (Reactive): -676.70VA
    Power Factor: -0.94
    Phase Angle: 0.00°
    Frequency: 50.00Hz
    Imported Energy (Active): 1551.37kWh
    Imported Energy (Active): 1335.69kWh
    Imported Energy (Reactive): 0.01kVAh
    Exported Energy (Reactive): 4362.14kVAh
    Total Demand Power (Active): 1668.02W
    Maximum Total Demand Power (Active): 3347.26W
    Import Demand Power (Active): 0.00W
    Maximum Import Demand Power (Active): 3347.26W
    Export Demand Power (Active): 1668.02W
    Maximum Export Demand Power (Active): 2109.45W
    Total Demand Current: 7.57A
    Maximum Total Demand Current: 14.97A
    Total Energy (Active): 2887.07kWh
    Total Energy (Reactive): 0.00kVAh

Holding Registers:
    Demand Time: 1s
    Demand Period: 60s
    Relay Pulse Width: 60ms
    Network Parity Stop: N-1
    Meter ID: 1
    Baud Rate: 9600
    P1 Output Mode: Export Energy (Active)
    Display Scroll Timing: 0s
    P1 Divisor: 0.001kWh/imp
    Measurement Mode: 0
    Pulse/LED Indicator Mode: Import + Export Energy (Active)

连接

如果您希望使用 Modbus TCP,以下参数是相关的:

host = IP or DNS name of your Modbus TCP gateway, required
port = TCP port of the Modbus TCP gateway, required
unit = Modbus device address, default=1, optional

如果您使用的是 Modbus RTU 连接,您可以指定:

device = path to serial device, e.g. /dev/ttyUSB0, required
baud = baud rate of your SDM unit, defaults to factory default, optional
unit = Modbus device address, defaults to 1, optional

连接仪表:

    >>> import sdm_modbus

    # SDM120 over Modbus TCP
    >>> device = sdm_modbus.SDM120(host="10.0.0.123", port=502)

    # SDM630 over Modbus RTU
    >>> device = sdm_modbus.SDM630(device="/dev/ttyUSB0", baud=9600)

测试连接:

    >>> device.connected()
    True

打印对象会产生基本的设备参数:

    >>> device
    SDM120(10.0.0.123:502, connectionType.TCP: timeout=1, retries=3, unit=0x1):

连接到多个设备

parent通过在创建新实例时提供已连接的设备,可以重新使用现有的 RTU 或 TCP 连接。如果 Modbus TCP 网关只接受有限数量的连接,或者您希望在同一总线上寻址多个 RTU 设备,这可能是必要的。例如:

    # Connect to a SDM630 over Modbus TCP
    >>> device_1 = sdm_modbus.SDM630(host="10.0.0.123", port=502, unit=1)

    # Connect to a SDM630 using the existing connection
    >>> device_2 = sdm_modbus.SDM630(parent=device_1, unit=2)

读取寄存器

按名称读取单个输入寄存器:

    >>> device.read("voltage")
    236.89999389648438

通过将sdm_modbus.registerType.INPUT枚举传递给 来读取所有输入寄存器read_all()。将此留空以读取INPUTHOLDING寄存器:

    >>> device.read_all(sdm_modbus.registerType.INPUT)
    {
        "voltage": 238.60000610351562,
        "current": 7.59499979019165,
        "power_active": -1673.800048828125,
        "power_apparent": 1797.5904541015625,
        "power_reactive": -655.4000244140625,
        "power_factor": -0.9311425685882568,
        "phase_angle": 0.0,
        "frequency": 50.0,
        "import_energy_active": 1556.35595703125,
        "export_energy_active": 1345.9210205078125,
        "import_energy_reactive": 0.014999999664723873,
        "export_energy_reactive": 4376.02001953125,
        "total_demand_power_active": 1659.360107421875,
        "maximum_total_demand_power_active": 3347.26318359375,
        "import_demand_power_active": 0.0,
        "maximum_import_demand_power_active": 3347.26318359375,
        "export_demand_power_active": 1659.360107421875,
        "maximum_export_demand_power_active": 2109.4541015625,
        "total_demand_current": 7.531858921051025,
        "maximum_total_demand_current": 14.968546867370605,
        "total_energy_active": 2902.277099609375,
        "total_energy_reactive": 4376.03515625
    }

    >>> device.read_all(sdm_modbus.registerType.HOLDING)
    {
        "demand_time": 1,
        "demand_period": 60,
        "relay_pulse_width": 60,
        "network_parity_stop": 0,
        "meter_id": 1,
        "baud": 2,
        "p1_output_mode": 4,
        "display_scroll_timing": 0,
        "p1_divisor": 0,
        "measurement_mode": 0,
        "indicator_mode": 0
    }

写寄存器

也可以写入保持寄存器。设置新的波特率,例如:

    >>> device.write("baud", 2)
    WriteMultipleRegisterResponse (28,2)

您需要通过按住设置按钮 5 秒钟来启用设备上的设置模式Exception Response(134, 6, GatewayNoResponse),否则您将收到一个或类似的信息。

注册详情

如果您需要有关特定寄存器的更多信息,以查找单位或枚举,例如:

    >>> device.registers["voltage"]
        # address, length, type, datatype, valuetype, name, unit, batching
        (
            0,
            2,
            <registerType.INPUT: 1>,
            <registerDataType.FLOAT32: 11>,
            <class 'float'>,
            'Voltage',
            'V',
            1
        )

    >>> device.registers["p1_divisor"]
        # address, length, type, datatype, valuetype, name, unit, batching
        (
            63760,
            2,
            <registerType.HOLDING: 2>,
            <registerDataType.FLOAT32: 11>,
            <class 'int'>,
            'P1 Divisor',
            ['0.001kWh/imp', '0.01kWh/imp', '0.1kWh/imp', '1kWh/imp'],
            2
        )

贡献

非常欢迎贡献,尤其是在支持的单元上进行测试,并添加其他 Eastron SDM 单元。